Plate and Frame Heat Exchangers

Author: Steve

Aug. 26, 2024

15 0 0

Plate and Frame Heat Exchangers

 

For more information, please visit HPE.

Introduction

In 41 Cooper Square, the boilers and chillers supply primary water used to heat or cool the building.  However, the water supplied by these systems is not directly routed to the radiative copper piping. Instead, a secondary flow of water is used throughout the network of radiant panels. In the case of heating, plate and frame heat exchangers are used to transfer heat from the primary hot water (from the boiler) to a secondary flow that supplies hot water to the radiant panels for heating. In order to cool the building, heat is rejected from the secondary flow to the primary chilled water supplied by the chillers. Both the heating and cooling systems have their own heat exchanger, which supplies hot and cold secondary flows that are routed to specified locations throughout the building. Figure 1 is a photograph of a chiller-side heat exchanger and Figure 2 is general schematic of a heat exchanger with temperatures typical of the heating mode.

 

Figure 1. Heat exchanger for chiller system.

Figure 2. Schematic of heat exchanger for boiler system.

 

 

 

 

 

 

 

 

 

 



Background

Plate and Frame Heat Exchangers:

There are many different types of heat exchangers, all utilizing different geometric configurations in order to achieve different design objectives. In a plate and frame heat exchanger, a series of parallel plates are joined together with equidistant gaps between them. Each of the two working fluids is passed through alternating chambers, maximizing the surface area over which heat can be transferred via conduction through the metal plates. This flow pattern is shown in Figure 3, provided by a manufacturer of industrial heat exchangers similar to those used in 41 Cooper Square.

 

Figure 3. Plate and Frame Heat Exchanger Flow. [1]

 

 

 

 

 

 

 

 

 

The two fluids in the heat exchanger are never mixed, creating two completely independent flows. Using plate and frame heat exchangers has the advantage of allowing the boiler (or the chiller&#;s evaporator) pressure to remain relatively low, as the primary flow does not have to be routed throughout the building&#;s radiant panels. Additionally, the secondary flow can more easily be routed to different parts of the building in response to changing cooling and heating demands without affecting the operation of the boiler (or chiller).

Figure 4. BMS Primary and Radiant Hot Water Heat Exchanger Panel.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The secondary flow is circulated throughout the building&#;s radiant panels using the two pumps labeled 'HWP1&#; and &#;HWP2&#; shown in Figure 4. These pumps both are controlled by Variable Frequency Drives (VFDs) that allow the BMS to regulate the flow rate produced by each pump. The BMS adjusts the flow produced by the pumps to maintain a differential pressure of 15 psi in the secondary water loop (as measured by the differential pressure sensor Figure 4) [2].

The heat exchanger used in the building&#;s cooling system (Figure 5) uses primary chilled water from the chiller (or from the absorption chiller in the cogeneration plant or from the water-side free cooling plate and frame heat exchanger) to cool secondary chilled water flow for use in the radiant panels. To avoid condensation, the BMS monitors the secondary chilled water supply temperature, indoor air temperature, and humidity.  The radiant panel surface temperature is set to the greater of 3°F above dew point or 55°F to avoid condensation.

 

Figure 5. BMS Primary and Radiant Chilled Water Heat Exchanger Panel.

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional reading:
Key Questions to Ask When Sourcing Portable Emergency Shelters 5900mm Supplier

Are you interested in learning more about stainless steel heat exchanger tube? Contact us today to secure an expert consultation!

 

The flow produced by the pumps is routed to individual radiant panels using a large array of valves. Three way-valves in each room are individually controlled by the BMS to switch between allowing hot and cold secondary flow to enter the radiant panels. At the outlet of the radiant panels in every room, there are two servo valves, one for the hot and cold secondary return flows. By adjusting the position of these outlet servo valves, the flow rate through the radiant panels can be controlled while keeping the hot and cold secondary flows separate. The BMS panel of Figure 6 below shows the three-way valve that controls the radiant water inlet flow, and the two servo valves regulating the outlet flow in a classroom (505).

Figure 6. BMS Radiant Panel and Air Damper for Room 505.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control System Overview

The purpose of the heat exchanger is to produce secondary water flow at a specified temperature. The secondary flow rate is controlled as a function of differential pressure in the secondary flow loop. For example, if heating demand in the building increases, more radiant panels will be opened, and the differential pressure in the secondary hot water loop will fall due to the effective decrease in flow resistance. A differential pressure sensor detects this decrease in pressure (or "head"), and the BMS responds by increasing the operating speed of the secondary hot water pumps to increase flow rate and maintain a constant differential pressure of 15 psi in the secondary loop [2]. With the secondary flow rate controlled as a function of differential pressure, the controlled (or process) variable in the heat exchanger system is the secondary flow output temperature.

Figure 7. Heat exchanger schematic depicting servo valve to directly control primary flow.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controlled device, or actuator). By modulating the primary mass flow rate (the controlled agent), the secondary flow temperature can be controlled. For example, if the controller)detects that the secondary flow temperature is too low to meet current heating demands, the mass flow rate of primary hot water through the heat exchanger will be increased via the servo valve. By increasing the primary flow rate, there will be a greater mass of hot water in the heat exchanger at any given time, allowing more heat to be transferred from the primary flow to the secondary flow. The increase in heat transfer causes the secondary flow temperature to rise, making the secondary water temperature hotter in order to meet the higher heating load.   Lowering the primary flow rate would have the opposite result, decreasing the secondary flow temperature.  

As shown in Figure 7, the boiler nominally provides primary flow at 180 °F (82 °C) [3] . The primary hot water flow rate through the heat exchanger is modulated via the servo valve (the). By modulating the primary mass flow rate (the), the secondary flow temperature can be controlled. For example, if the BMS (thedetects that the secondary flow temperature is too low to meet current heating demands, the mass flow rate of primary hot water through the heat exchanger will be increased via the servo valve. By increasing the primary flow rate, there will be a greater mass of hot water in the heat exchanger at any given time, allowing more heat to be transferred from the primary flow to the secondary flow. The increase in heat transfer causes the secondary flow temperature to rise, making the secondary water temperature hotter in order to meet the higher heating load. Lowering the primary flow rate would have the opposite result, decreasing the secondary flow temperature.

The secondary flow exit temperature is controlled through modulation of the primary mass flow rate. It should be noted, however, that this mass flow rate modulation would also affect the exit temperature of the primary flow. By increasing the primary mass flow rate, more heat transfer will occur, but the primary flow itself will exit at a higher temperature. As the hot primary flow passes through the heat exchanger more rapidly, it does not remain in contact with the cool secondary flow long enough to experience a large temperature drop. It is counterintuitive for this higher exit temperature to result in greater heat transfer, but physical laws (the enthalpy of water at these operating ranges) dictate that mass flow rate, not fluid temperature, has a dominant effect on heat transfer processes.

Since the primary flow comes out of the heat exchanger at a higher temperature at these high flow rates, it will require less fuel to be heated back to the 180 °F set point in the boiler. The BMS takes this information into consideration, determining primary flow rates that will produce secondary flow at the necessary temperature to meet thermal loads, while minimizing fuel consumption in the boilers by maximizing the primary flow&#;s exit temperature from the heat exchanger [2]. 

Variable Frequency Drive: Device that modulates the frequency of the current input to an AC motor (usually driving a pump or fan) in order to control the motor&#;s speed and power consumption.

Enthalpy: The sum of a fluid&#;s potential and flow energy. This measure of flow energy is covered thoroughly in Thermodynamics and Heat Transfer.

[1] http://www.dhtnet.com/plate_frame_heat_exchangers_as.htm

[2] Gruzen Sampton, Sequence of Operation &#; The New Academic Building of Cooper Union, Morphosis Architects, Los Angeles, CA, Rep. , June . p. 20.

[3] GMP Energy Report &#; The New Academic Building of Cooper Union, IBE Consulting Engineers, Camarillo, CA, , p. 16.

Plate Heat Exchangers Working Principle

Generally, these plates are corrugated in order to increase the turbulence, the thermal exchange surface and to provide mechanical rigidity to the exchanger. Corrugation is achieved by cold forging of sheet metal with thicknesses of 0.3mm to 1 mm.

The most frequently used materials for the plates are stainless steel (AISI 304, 316), titanium and aluminium.

The corrugation on the plates forces the fluid on a tortuous path, setting a space between two adjacent plates b, from 1 to 5 millimeters.

The fluids can cross the channels in series (a less common solution) or in parallel by making counter-current or current configurations.

The serial configuration is used when there is a small flow rate for each fluid but high heat jump; the greatest problem is with a high pressure drop and an imperfect counter-current.

The parallel configuration with countercurrent channels is used for high flow rates with moderate temperature drops, and is the most widely used.

When there is a great difference between the flow rates (or between the maximum permissible pressure drop) of the two fluids, the exchanger can run twice by the fluid with a lower flow (or higher losses) to balance the values of pressure drops or specific flow rates in the channels.

The figure shows the different configurations: in parallel, in series and mixed

One of the most common problems for plate heat exchangers is an irregular supply of the all channels in parallel. In fact, the fluid tends to distribute in greater quantities in the first channels rather than the last ones in order to balance the pressure drop.

As the number of plates increases, even distribution declines, resulting in a decrease in the overall performance of the exchanger.
There are two basic types of plate heat exchangers: BPHE-Brazed Plate Heat Exchangers and PHE-Plate Heat Exchangers.

If you want to learn more, please visit our website inconel 625 tubing.